Lapp N2XH and N2XCH - Direct Burial Cable

N2XH Halogen-free power cable

Application range

  • Alternative to the PVC installation cable NYY-J, NYY-O
  • For installation on or under the plaster
  • Fixed installation indoor, in air or concrete
  • For buildings or industrial plants with a high density of people or valuable assets
  • No direct burial or installation in water
  • Outdoor laying only when protected from direct sunlight and other external impacts

Product features

  • Flame-retardant according IEC 60332-1-2
  • No flame-propagation according to IEC 60332-3-24
  • Halogen-free according to IEC 60754-1 (amount of halogen acid gas)
  • Corrosiveness of combustion gases according to IEC 60754-2 (degree of acidity)
  • Low smoke density according to IEC 61034-2

Technical Data

  • Low voltage power cable Classification ETIM 6: ETIM 6.0 Class-ID: 
  • Core identification code: Up to 5 cores: colour-coded according to VDE 0293-308
  • From 6 cores: black with white numbers
  • Minimum bending radius:
  • Single-core: 15 x outer diameter 
  • Multi-core: 12 x outer diameter
  • Nominal voltage: U0/U: 0.6/1.0 kV
  • Test voltage: 4000 V 
  • Temperature range: During installation: -5°C to +90°C Fixed installation: -40°C to +90°C